Induced Voltage Discovered During Safe Energy Check
2426 Views
Feedback
0 Comments

Favorite
Image for Induced Voltage Discovered During Safe Energy Check

Type:  Lessons Learned

Publisher:  CH2MHill Plateau Remediation Company (Richland, WA - Hanford Site), Richland, WA - Hanford Site (CHPRC)

Published As:  Public

Date: 

Topics:  Electrical, Maintenance

While performing a safe energy check for a lockout/tagout, alternating current (ac) voltage was found when only direct current (dc) voltage was expected. Since an ac voltage was not expected, the work was stopped to determine the source of the ac voltage.

Lesson Learned: Alternating current energy can be measured on a direct current system, due to induced alternating current from the system, depending on where the voltage measurements are taken and due to use of a voltmeter that will automatically measure ac and dc voltages.

You must be logged in to open the attachment.

Download Article
Comments about this Article
You must be logged in to add or view comments.
Related Articles
Feedback Form
How did you apply this information?
You must be logged in to use this feature
Is this article applicable to your organization?