Circuit Verification Missed Secondary Power Source
2653 Views
Feedback
0 Comments

Favorite
Image for Circuit Verification Missed Secondary Power Source

Type:  Lessons Learned

Publisher:  Washington River Protection Solutions, Hanford Site (WRPS)

Published As:  Public

Date: 

Topics:  Electrical, Operations, Hazardous Energy Control

Assumptions made during circuit verifications pointed to a particular breaker as isolating power and failed to identify a secondary power source. During circuit verifications, confirm that a single breaker, when isolated, removes electricity from a particular component. This may require returning power to all other circuits to make a positive identification. Diligence and methodical performance of circuit verifications is required as encountering out-of-normal wiring configuration (anomalies) is not uncommon.